Paroc Pro Segment DL 140 kg/m³

Paroc Pro Segment 100 DL is a ready cut segment in double layer for medium and big pipe elbows made of non-combustible stone wool pipe section. This industrial made insulation parts give the best insulation solution for big pipe elbows without heat bridges.

Certification Number

0809-CPR-1016 / VTT Expert Services Ltd, P.O. Box 1001, FI-02044 VTT, Finland, 9.6.2014

Designation Code

MW-EN 14303-T8/T9-ST(+)680-WS1-CL10

 

Nominal Density

140 kg/m³

Maximum Service Temperature

Description

Value

In accordance with

Maximum Service Temperature (Declared), ST(+)i

680 °C

EN 14707

Τα  προϊόντα πετροβάμβακα είναι ικανά να αντέχουν σε υψηλές θερμοκρασίες. Το συνδετικό υλικό αρχίζει να εξατμίζεται όταν η θερμοκρασία του υπερβαίνει περίπου   200 °C. Οι μονωτικές ιδιότητες παραμένουν αμετάβλητες, αλλά η θλίψη στρες αποδυναμώνει. Η θερμοκρασία τήξης των προϊόντων πετροβάμβακα είναι πάνω από 1000 °C.

Dimensions

Thickness

Inner Diameter

80 - 160 mm

219 - 914

In accordance with EN 13467

In accordance with EN 13467

Άλλες διαστάσεις είναι διαθέσιμες κατόπιν ζήτησης

Fire Properties

Reaction to Fire

Essential characteristics

Performance

Harmonised technical specification (method standard)

Reaction to Fire, Euroclass

A1L

EN 14303:2009 (EN 13501-1)

Thermal Properties

Thermal Resistance

Essential characteristics

Performance

Harmonised technical specification (method standard)

Thermal Conductivity (declared) in 50 °C, λ50

0.042 W/mK

EN 14303:2009+A1:2013 (EN ISO 8497)

Thermal Conductivity (declared) in 100 °C, λ100

0.047 W/mK

EN 14303:2009+A1:2013 (EN ISO 8497)

Thermal Conductivity (declared) in 200 °C, λ200

0.065 W/mK

EN 14303:2009+A1:2013 (EN ISO 8497)

Thermal Conductivity (declared) in 300 °C, λ300

0.087 W/mK

EN 14303:2009+A1:2013 (EN ISO 8497)

Thermal Conductivity (declared) in 400 °C, λ400

0.115 W/mK

EN 14303:2009+A1:2013 (EN ISO 8497)

Dimensions and Tolerances

T8/T9

EN 14303:2009+A1:2013 (EN 14303)

Moisture Properties

Water Permeability

Essential characteristics

Performance

Harmonised technical specification (method standard)

Water Absorption, Short Term WS, Wp

≤ 1 kg/m²

EN 14303:2009+A1:2013 (EN 13472)

Rate of Release of Corrosive Substances

Trace Quantities of Water Soluble Ions and the pH Value

Essential characteristics

Performance

Harmonised technical specification (method standard)

Chloride Ions, Cl-

< 10 ppm

EN 14303:2009+A1:2013 (EN 13468)

Durability

Durability of Reaction to Fire Against Ageing/Degradation:

The fire performance of mineral wool does not deteriorate with time. The Euroclass classification of product is related to the organic content, which cannot increase with time.

Durability of Reaction to Fire Against High Temperature:

The fire performance of mineral wool does not deteriorate with high temperature. The Euroclass classification of the product is related to the organic content, which remains constant or decreases with high temperature.

 

Durability of Thermal Resistance Against Ageing/Degradation:

Thermal conductivity of mineral wool products does not change with time, experience has shown the fibre structure to be stable and the porosity contains no other gases than atmospheric air.

Maximum Service Temperature - Dimensional Stability

680 °C / EN 14303:2009+A1:2013 (EN 14707)

Durability of Thermal Resistance Against High Temperature: